What COP Value is Considered Acceptable for a Refrigeration Unit?
2026.11.19
refrigeration unit
The COP (Coefficient of Performance) compliance value of a refrigeration unit is entirely determined by the unit type, cooling method, cooling capacity range, and operating conditions. The current mandatory national standard GB 19577-2024 (implemented on February 1, 2025) represents the minimum compliance threshold for market access.
1. Minimum Compliance Value for Ambient Temperature Industrial Chillers
This is the most commonly used compliance benchmark for industrial refrigeration units. The test conditions are chilled water outlet temperature of 7°C and cooling water inlet temperature of 30°C.
Water-cooled units:
Cooling capacity < 528kW: COP ≥ 5.0 is the standard for Level 3, Level 2 ≥ 5.8, Level 1 ≥ 6.1
Cooling capacity ≥ 528kW: COP ≥ 5.2 is the standard for Level 3, Level 2 ≥ 6.0, Level 1 ≥ 6.3
Air-cooled units:
Cooling capacity ≤ 50kW: COP ≥ 2.8 is the standard for Level 3, Level 2 ≥ 3.2, Level 1 ≥ 3.6
50kW < Cooling capacity < 528kW: COP ≥ 3.0 is the standard for Level 3, Level 2 ≥ 3.4, Level 1 ≥ 3.8
Cooling capacity ≥ 528kW: COP ≥ 3.2 is the standard for Level 3, Level 2 ≥ 3.6, Level 1 ≥ 4.0
2. Actual reference values for low-temperature operating conditions
In low-temperature scenarios, the evaporation temperature decreases significantly, and the COP will naturally decrease. The standard values for normal temperatures cannot be directly applied.
Standard 0℃~-10℃ low-temperature units: COP ≥ 2.8 is considered acceptable; high-quality models can reach 3.2 or higher.
-20℃ low-temperature units: COP ≥ 2.2 is the industry standard; high-efficiency models can exceed 2.6.
-40℃ and below cascade ultra-low temperature units: COP is generally in the 1.0~1.8 range; above 1.2 is considered acceptable.
3. Special Compliance Requirements for Commercial Building Scenarios
In addition to meeting the basic national standard threshold, refrigeration units for public buildings have additional requirements depending on the climate zone.
Ordinary public building water-cooled/evaporative chiller units: COP not lower than 4.2.
Projects in hot-summer and cold-winter regions: COP requirement increased to 4.3; in severely cold Zone A, it can be relaxed to 4.1.
Green building three-star/low-carbon building projects: require an additional 12% improvement on the basic compliance value; for example, a standard centrifugal chiller with a COP of 5.6 needs to reach 6.28 or higher.